Our Products
- Energy saving dampers K100/K200
- Control & balance dampers K300/K400
- PVC dampers for corrosive atmospheres K500-PVC
- Special application dampers K500 X PVC
- Non-return dampers B range
- Heavy duty circular dampers KHDC
- Heavy duty rectangular dampers KHDR-CD
- Heavy duty non-return dampers KHDR-NR
- Perforated face diffusers KP range
- External weather louvres KWL range
Energy Saving Dampers
Multi-leaf dampers primarily used in air conditioning and ventilation systems for volume control and isolation
K100-U Ultra low leakage energy saving damper
-
Please contact our Technical Sales Team for full Product Specification Details
Description:
- K100‐U Ultra low leakage energy saving volume control damper (Insulated Blades). Blade leakage in accordance with DIN 1946 part4
Applications:
- Multi‐leaf dampers primarily used in air conditioning and ventilation systems for volume control, pressure control and isolation
- This range of dampers are energy saving, reducing air loss considerably over standard products. The K100‐U incorporate insulated blades for improved thermal performance and noise reduction
- Direct fixing to the inlet louvres to form one assembly
- Room isolation in manufacture of pharmaceutical products
- Agricultural stores
- System sterilization
Features:
- K100‐U ultra low leakage dampers meet the stringent DIN 1946 part 4 standard for blade leakage
- K100‐U dampers incorporate thermal insulation within the blade section
- High strength galvanised channel casing
- Aerofoil section extruded aluminium blade with integral blade edge seal
- Opposed blade action for optimum air control
- Full Length 12.7mm square drive shaft
- Individual blade coupling by plastic gears, running in maintenance free acetal bushes, forming a non ferrous gearing system
- Manual, electrical or pneumatic control options
- Large single and multiple module assemblies
- Circular Spigot or Flanged connections available
- Face and bypass dampers
Construction:
- Casing – 1.2mm thick galvanised mild steel casing, 132mm deep and 40mm flanges c/w 10mm return edge for flange clamps
- Blades – Aerofoil section extruded aluminium blades, 103mm wide c/w EPDM edge seals. K100‐U blade sections filled with thermal insulation
- Gears – Plastic gear with integral stub spindle. K100‐U gear fitted with foam/felt side seals running on low friction PTFE strip
- Bushes – 25mm diameter hard acetal, incorporating locking rib. Bushes encased as standard
Size Range:
- K100‐U – 100 W x 108 H to 1000 W x 1008 H in a single module
- For larger multiple module assemblies, please consult our technical department
- Circular, flat oval, spigot & flanged units are available
Operating Conditions:
- Temperature: ‐10°C to +90°C
- Pressure: ± 2500Pa
- Velocity: up to 20m/s
Options:
- Damper casing materials of 316 grade stainless steel, Aluminium and PVC
- Dampers incorporating oilite bearings
- External linkages or gears
- Parallel bladed dampers
- Face and bypass dampers
- Damper casings to suit customer requirements
- Flange drillings
- Powder coated casing & blades in either Epoxy or Polyester
- Concealed Motors
Control Options:
- M = Manual operated quadrant
- E = Extended spindle for motorization (by others)
Factory Fitted Actuators:
- Electrical actuator options – 24/110/240 volt units. Double acting /open‐close, modulating, spring return
- Pneumatic actuator options. Double acting/open‐close, modulating, spring return
K200 Low leakage energy saving damper
-
Please contact our Technical Sales Team for full Product Specification Details
Description:
- K200 Low leakage isolation volume control damper
Applications:
- Multi‐leaf dampers primarily used in air conditioning and ventilation systems for volume control, pressure control and isolation
- This range of dampers are energy saving, reducing air loss considerably over standard products.
- Direct fixing to the inlet louvres to form one assembly
- Room isolation in manufacture of pharmaceutical products
- Agricultural stores
- System sterilization
Features:
- Aerofoil section extruded aluminium blade with integral blade edge seal
- Opposed blade action for optimum air control
- Full Length 12.7mm square drive shaft
- Individual blade coupling by plastic gears, running in maintenance free acetal bushes, forming a non ferrous gearing system
- Manual, electrical or pneumatic control options
- Large single and multiple module assemblies
- Circular Spigot or Flanged connections available
- Face and bypass dampers
Construction:
- Casing – 1.2mm thick galvanised mild steel casing, 132mm deep and 40mm flanges c/w 10mm return edge for flange clamps
- Blades – Aerofoil section extruded aluminium blades, 103mm wide c/w EPDM edge seals.
- Gears – Plastic gear with integral stub spindle.
- Bushes – 25mm diameter hard acetal, incorporating locking rib. Bushes encased as standard
Size Range:
- K200 – 100 W x 108 H to 1250 W x 1250 H in a single module
- For larger multiple module assemblies, please consult our technical department
- Circular, flat oval, spigot & flanged units are available
Operating Conditions:
- Temperature: ‐10°C to +90°C
- Pressure: ± 2500Pa
- Velocity: up to 20m/s
Options:
- Damper casing materials of 316 grade stainless steel, Aluminium and PVC
- Dampers incorporating oilite bearings
- External linkages or gears
- Parallel bladed dampers
- Face and bypass dampers
- Damper casings to suit customer requirements
- Flange drillings
- Powder coated casing & blades in either Epoxy or Polyester
- Concealed Motors
Control Options:
- M = Manual operated quadrant
- E = Extended spindle for motorization (by others)
Factory Fitted Actuators:
- Electrical actuator options – 24/110/240 volt units. Double acting /open‐close, modulating, spring return
- Pneumatic actuator options. Double acting/open‐close, modulating, spring return
K200-U Ultra low leakage energy saving damper
-
Please contact our Technical Sales Team for full Product Specification Details
Description:
- K200‐U Ultra low leakage isolation volume control damper. Blade leakage in accordance with DIN 1946 part 4
Applications:
- Multi‐leaf dampers primarily used in air conditioning and ventilation systems for volume control, pressure control and isolation
- This range of dampers are energy saving, reducing air loss considerably over standard products.
- Direct fixing to the inlet louvres to form one assembly
- Room isolation in manufacture of pharmaceutical products
- Agricultural stores
- System sterilization
Features:
- K200‐U ultra low leakage dampers meet the stringent DIN 1946 part 4 standard for blade leakage
- Aerofoil section extruded aluminium blade with integral blade edge seal
- Opposed blade action for optimum air control
- Full Length 12.7mm square drive shaft
- Individual blade coupling by plastic gears, running in maintenance free acetal bushes, forming a non ferrous gearing system
- Manual, electrical or pneumatic control options
- Large single and multiple module assemblies
- Circular Spigot or Flanged connections available
- Face and bypass dampers
Construction:
- Casing – 1.2mm thick galvanised mild steel casing, 132mm deep and 40mm flanges c/w 10mm return edge for flange clamps
- Blades – Aerofoil section extruded aluminium blades, 103mm wide c/w EPDM edge seals.
- Gears – Plastic gear with integral stub spindle.K200‐U gear fitted with foam/felt side seals running on low friction PTFE strip
- Bushes – 25mm diameter hard acetal, incorporating locking rib. Bushes encased as standard
Size Range:
- K200‐U – 100 W x 108 H to 1000 W x 1008 H in a single module
- For larger multiple module assemblies, please consult our technical department
- Circular, flat oval, spigot & flanged units are available
Operating Conditions:
- Temperature: ‐10°C to +90°C
- Pressure: ± 2500Pa
- Velocity: up to 20m/s
Options:
- Damper casing materials of 316 grade stainless steel, Aluminium and PVC
- Dampers incorporating oilite bearings
- External linkages or gears
- Parallel bladed dampers
- Face and bypass dampers
- Damper casings to suit customer requirements
- Flange drillings
- Powder coated casing & blades in either Epoxy or Polyester
- Concealed Motors
Control Options:
- M = Manual operated quadrant
- E = Extended spindle for motorization (by others)
Factory Fitted Actuators:
- Electrical actuator options – 24/110/240 volt units. Double acting /open‐close, modulating, spring return
- Pneumatic actuator options. Double acting/open‐close, modulating, spring return
Back to top